Typ: Świetlne kurtyny bezpieczeństwa i czujniki bezpieczeństwa
Symbol: SQ4-A22-P
Producent: Panasonic
Waga produktu: 45g
Minimalna ilość w zamówieniu: 1
Ilość produktów w opakowaniu jednostkowym: 1
Czujnik bezpieczeństwa wycieku cieczy SQ4
Safety Liquid Leak Sensor [Control Category 4 PLe SIL3] SQ4
Item | Specifications |
---|---|
Product Number | SQ4-A22-P |
Part Number | SQ4-A22-P |
CE marking directive compliance | Machinery Directive, EMC Directive, RoHS Directive |
Sensing object | Sulfuric acid, Hydrochloric acid,Phosphoric acid, Ammonia, Fluorinert (Note 2), Galden (Note 2), Hydrofl uoric acid etc. (Note 3) (Note 1) Highly viscous liquid may not be stably detected. (Note 2) The agents mentioned above are examples. It may not be detected depending on viscosity the agent.Before using this device, check the detecting liquid and installation condition. (Note 3) Fluorinert is the world wide trademark of 3M. Galden is the registered trademark of Solvay. |
Power voltage | 12 to 24 V DC plus or minus 10 % Ripple P-P 10 % or less |
Current consumption | 30 mA or less |
Utilization category | DC-12, DC-13 |
Detection output(Leakage detection) | PNP open-collector transistor - Maximum source current: 50 mA - Applied voltage: Same as the supply voltage (between detection output and +V) - Residual voltage: 2.5 V or less (at 50 mA source current) |
Detection output(Leakage detection):Response time | 10 ms or less |
Detection output(Leakage detection):Output operation | ON when normal condition or initial detection, OFF when detection leakage or wrong installation |
Detection output(Leakage detection):Short-circuit protection | Incorporated |
Detection auxiliary output(Initial detection) | PNP open-collector transistor - Maximum source current: 50 mA - Applied voltage: Same as the supply voltage (between detection auxiliary output and +V) - Residual voltage: 2.5 V or less (at 50 mA source current) |
Detection auxiliary output(Initial detection):Response time | 50 ms or less |
Detection auxiliary output(Initial detection):Output operation | ON when normal condition, OFF when initial detection or accidental leakage |
Detection auxiliary output(Initial detection):Short-circuit protection | Incorporated |
Protection | IP65 / IP67 (IEC) |
Ambient temperature | -10 to +55 ℃ +14 to +131 ℉ (No dew condensation or icing allowed) (Note) Storage: -10 to +55 ℃ +14 to +131 ℉ (Note) Liquid being detected should be also kept within the rated ambient temperature range. |
Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH |
Emitting element | Infrared LED (modulated) |
Material | Enclosure: PFA |
Cable | 0.1 mm2 4-core PFA cabtyre cable, 2 m 6.562 ft long |
Weight | Net weight: 45 g approx Gross weight: 110 g approx |