HGF13AAN


Typ: Czujniki pomiarowe

Symbol: HG-F13A-A-N

Producent: Panasonic

Waga produktu: 85g

Minimalna ilość w zamówieniu: 1

Ilość produktów w opakowaniu jednostkowym: 1

Opis produktu


Czujnik TOF do pomiarów dalekiego zasięgu,

Item Specifications
Product Number HG-F13A-A-N
Part Number HG-F13A-A-N
Measurable range 250 to 3,000 mm 9.843 in to 118.110 in
Displayable range 200 to 3,300 mm 7.874 in to 129.921 in
(Note 2):When an object is detected, the range of numerical values that appear on the digital display is regarded as the displayable distance. When zero setting is performed, the displayable distance varies depending on the zero setting distance.
Repeatability 10 mm 0.394 in or less (target object: sheet of white non-glossy paper measuring 200 × 200 mm 7.874 × 7.874 in)
Hysteresis 30 mm 1.181 in (default setting) Possible to vary up to 1 mm 0.039 in minimum in the PRO mode (Note 3)
(Note3):Changing the hysteresis may result in unstable sensing. After making a change, perform operation check using actual equipment.
Linearity ± 2% F.S. (Note 4) (at a measuring distance of 500 mm to 3,000 mm 19.685 in to 118.110 in)
(Note 4):F.S. (full scale) represents a range from 0 mm to 3,000 mm 0 in to 118.110 in.
Temprerature characteristics 0.1% F.S./℃
Light source Red semiconductor laser: Class 1 [JIS / IEC / GB / KS / FDA(Note)]
Maximum output: 0.39 mW, Peak emission wavelength: 680 nm 0.0268 mil
(Note) : This product complies with the FDA regulations (FDA 21 CFR 1040.10 and 1040.11) in accordance with FDA Laser Notice No. 56, except for complying with IEC 60825-1 Ed. 3.
Beam diameter Approx. ø10 mm ø0.394 in (typical) (at the measuring distance of 1,000 mm 39.370 in)
(Note 5):The beam diameter is defined as 1/e2 (approx. 13.5%) of the center light intensity. Due to leak light outside the defined range, the measurement values may be affected if the reflectance around the detecting point is higher than that of the detecting point.
Supply voltage 24 V DC ±10%, including 10% ripple (P-P)
Current consumption 40 mA or less (at 24 V DC supply voltage)
(Note 6):Analog output is not included.
Control output NPN open-collector transistor
• Maximum sink current: 50 mA
• A pplied voltage: 30 V DC or less (Between control output to 0 V)
• Residual voltage: 1.5 V or less (At 50 mA sink current)
• Leakage current: 0.1 mA or less
Control output:Output operation Switchable between Light-ON / Dark-ON, (Default: Light-ON)
Control output:Short-circuit protection Incorporated (Auto reset type)
Analog output Switchable between voltage output / current output (Default: voltage output)
Analog output:Analog voltage output:Output range • In normal operation: 0 to +5 V Possible to set the distance range (Default: 250 to 3,000 mm 9.843 in to 118.110 in)
• When alarm occurs: Last value is held or the range is set to 0 V on the near point side and to +5.2 V on the far point side.
(Note) : When the intensity of received light is unstable, the voltage is output as 0 V and the current is output as 0 mA.
Analog output:Analog voltage output:Output impedance 100 Ω
Analog output:Analog current output:Output range • In normal operation: +4 mA to +20 mA Possible to set the distance range (Default: 250 to 3,000 mm 9.843 in to 118.110 in)
• When alarm occurs: Last value is held or the range is set to 0 mA on the near point side and to +20.8 mA on the far point side.
(Note) : When the intensity of received light is unstable, the voltage is output as 0 V and the current is output as 0 mA.
Analog output:Analog current output:Output impedance 250 Ω or less
Response time Switchable between 35 ms / 100 ms / 300 ms / 2,000 ms (Default: 100 ms)
External input NPN non-contact input
• Input condition
Invalid: +8 to + V DC or Open
Valid: 0 to +1.2 V DC
• Input impedance: approx. 10 kΩ
External input function Switchable between zero set, teaching, or emission stop (Default: zero set)
Teaching function Switchable between normal sensing mode (2-point / limit) or window comparator mode (1-point / 2-point / 3-point)
(Default: Normal sensing mode)
Timer function Switchable between OFF / ON delay / OFF delay / one-shot (Default: OFF)
Timer period Switchable between 5 ms / 10 ms / 25 ms / 50 ms / 100 ms / 250 ms / 500 ms / 1,000 ms / 5,000 ms (Default: 5 ms)
Pollution degree 2
Overvoltage category Category I
Operating altitude 2,000 m 6561.680 ft or less
(Note 7):Do not use or store this product in environments where ambient air is pressurized to an air pressure higher than the atmospheric pressure at an altitude of 0 m.
Protection IP67 (IEC)
Ambient temperature -10 to +45 ℃ +14 to 113 ℉ (No dew condensation or icing allowed), Storage: -20 to +60 ℃ -4 to 140 ℉
Ambient humidity 35 to 85% RH, Storage: 35 to 85% RH
Ambient illuminance Incandescent light: 3,000 ℓx or less at the light-receiving face
Vibration resistance 10 to 55 Hz (period: 1 min.) frequency, 1.5 mm 0.059 in double amplitude in X, Y and Z directions for two hours each
Shock resistance 500 m/s2 acceleration (approx. 50 G) in X, Y and Z directions three times each
Cable 0.2 mm2 5-core composite cable, 2 m 6.562 ft long
Cable extension Extension up to total 10 m 32.808 ft is possible with 0.3 mm2, or more, cable
Material Enclosure: Aluminum die-cast, Front cover: Acrylic, Cable: PVC
Weight Net weight: approx. 85 g, Gross weight: approx. 130 g

 

Regulations and Standards

Item Specifications
Conforming directives and conforming regulations:EU Regulations EMC Directive 2014/30/EU
Conforming directives and conforming regulations:UK Regulations EMC Regulations 2016/1091
Applicable standards EN 61000-6-4
EN 61000-6-2
USA regulations: FDA21 CFR1040.10, and 1040.11 (Laser Notice No.56 applied)
Conforming standards:USA/Canada Standards UL 61010-1
CAN/CSA No.61010-1
Conforming standards:Other standards IEC 60825-1
JIS C 6802
GB 7247.1
KS C IEC 60825-1

Mimo dołożenia wszelkich starań nie gwarantujemy, że publikowane dane techniczne oraz zdjęcia nie zawierają braków lub błędów. Ponieważ ewentualne błędy nie mogą być podstawą do roszczeń, w przypadku wątpliwości prosimy przed zakupem o kontakt z handlowcem.