Waga produktu: 150g
Minimalna ilość w zamówieniu: 1
Ilość produktów w opakowaniu jednostkowym: 1
Part Number | AGM1AD8 |
Product | Analog input unit |
Product name | Motion Controller GM1 |
Item | Specifications |
---|---|
Rated voltage | 24 V DC |
Operating voltage range | 20.4 to 28.8 V DC |
Allowable momentary power failure time | 10 ms |
Operating ambient temperature | 0 to +55℃ |
Storage ambient temperature | -40~+70 ℃ |
Operating ambient humidity | 10 to 95 % RH (at +25 ℃, no condensation or icing) |
Storage ambient humidity | 10 to 95 % RH (at +25 ℃, no condensation or icing) |
Dielectric strength (Leakage current: 5 mA) | 500 V AC for one minute *Please refer to the unit's specification sheet for details of breakdown voltage and insulation resistance. |
Insulation resistance (Test voltage: 500 V DC) | 100 MΩ or more *Please refer to the unit's specification sheet for details of breakdown voltage and insulation resistance. |
Vibration resistance | Compliant with JIS B 3502, IEC 61131-2 5 to 8.4 Hz, half amplitude 3.5 mm, 8.4 to 150 Hz acceleration 9.8 m/s2 10 sweeps each in X, Y and Z directions (1 octave/min) |
Shock resistance | Compliant with JIS B 3502, IEC 61131-2 147 m/s2, 3 times each in the X, Y, Z directions |
Noise resistance | 1000 V [p-p] with pulse widths of 1 μs and 50 ns (using a noise simulator) (Power supply terminal) |
Atmosphere | Free of corrosive gases No excessive dust |
European EU Standards | EMC: EN 61131-2 RoHS: EN IEC 63000 |
Overvoltage category | Category II |
Pollution degree | 2 |
Weight (main unit) | Approx. 150 g (including the terminal block) |
Consumption current | 160 mA or less |
Item | Specifications |
---|---|
No. of input points | 8 ch |
Input range (resolution) | Voltage: -10 to +10 V DC (Resolution: 1/64,000) 0 to +10 V DC (Resolution: 1/32,000) -5 to +5 V DC (Resolution: 1/64,000) 0 to +5 V DC (Resolution: 1/32,000) +1 to +5 V DC (Resolution: 1/25,600) *The full scale (F.S.) on the accuracy is from 0 to +5 V. Current: 0 to +20 mA (Resolution: 1/32,000) +4 to +20 mA (Resolution: 1/25,600) *The full scale (F.S.) on the accuracy is from 0 to +20 mA. |
Conversion speed | 50 μs/ch |
Exceeding the rated range | Possible to input up to the rated value ± 2% *When a value exceeding the rated value ±2% is set, the input is rounded to a value equivalent to the rated value ±2%. |
Total accuracy | ±0.2 %F.S. or less (at +25 ℃) ±0.4 %F.S. or less (at 0 to +55 ℃) |
Input impedance | Voltage input: Approximately 1 MΩ; current input: Approximately 250 Ω |
Absolute max. input | Voltage input: -15 V to +15 V; current input: -30 mA to +30 mA |
Insulation method | Between input terminals and internal circuit: Photocoupler and isolated DC/DC converter Between channels: Non-insulated |
Conversion execution / nonexecution channel settings | Possible to make non-converted channel settings. |
Input range selection | Possible to make settings on a channel-by-channel basis |
Average processing | Number of averaging times: Setting range of 2 to 60,000 times Time average: Time setting range of 1 to 1,500 ms Moving average: Setting range of 2 to 2,000 times |
Offset / Gain settings | A desired value within the digital output range can be set for the offset value. Setting range: -3,000 to +3,000 A desired value within the digital output range can be set for the gain value. Setting range: +9,000 to +11,000 (90 % to 110 %) |
Scale conversion settings | A desired value within the digital output range can be set for the scale conversion setting value. Setting range: -32768 to +32767 |
Upper limit / lower limit comparison | Output if the value is outside the preset upper limit or lower limit. Setting range: -32768 to +32767 |
Max. / Min. hold | Holding max. / min. values sampled |
Disconnection detection | Disconnection detection is possible for the following ranges. Possible to select auto or manual resetting. ・ 1 to 5 V range (Detection level: 0.7 V or less) ・ 4 to 20 mA range (Detection level: 2.8 mA or less.) |